Permit: T14BU00074

Parcel: 117042630


Addresses:

222 E 5TH ST

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
05/28/2014 FIRE SPKLR - FINAL Approved
05/27/2014 FIRE SPKLR - FINAL Denied 1. Need to move 2 heads from obstructions.
2. What is the reason for no head in west stairwell 1st floor?
05/16/2014 FIRE SPKLR - FINAL Denied 1. Remove tape from sprinkler heads.
2. Need to test water flow, tampers, and ITV with Alarm system.
3. Need copy of 5 year check valve service.
04/07/2014 FIRE SPKLR - FINAL Denied 1. 3rd floor hallways correct sprinkler coverage under duct work uprights are blocked
2. 1st floor correct sprinkler coverage blocked by round duct work in file room
3. Need 5 year check valve inspection completed
4. Need as bults for changes