Permit: T14BU00065

Parcel: 117072280


Addresses:

702 S 3RD AV

Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Date Description Inspector Results Comments
04/03/2014 POOL/SPA ELECTRIC Approved IVRS - Inspection :*
02/03/2014 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
02/03/2014 POOL/SPA ELECTRIC Partial Approval 1. OVERHEAD CLEARANCE OF SERVICE DROP WITHIN 10' OF WATERS EDGE DOES NOT MEET 22.5 FEET CLEARANCE OR 25' FROM TEP. CONSULT WITH TEP FOR DIRECTION
2. MAY HAVE TO RELOCATE SERVICE
3. NO UNDERGROUND ELECTRICAL TO EQUIP