Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T14BU00045
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/21/2014 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
03/21/2014 | MECHANICAL - FINAL | Approved | WILL CHECK GREASE RECEPTORS AT HOODS & PAINT ON EXPOSED DUCTS AT BUILDING FINAL | |
03/12/2014 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
03/12/2014 | MECHANICAL - FINAL | Partial Approval | HOODS, FANS, & DUCTS UP TO ROOF ARE ALL TYPE I. THE DUCTS ON ROOF CONNECTING FAN TO GREASE DUCT ARE NOT TYPE I & ARE NOT WELDED. THE CLEANOUT ACCESS IS NOT TYPE I. PROVIDE HINGE KITS ON 2 FANS & GREASE RECEPTORS. EXTEND DISCHARGE ON SMALL FAN ABOVE MAKEUP AIR UNIT & PARAPET WALL. GAS BAKERY OVEN REQUIRES A TYPE II HOOD. ELEC BAKERY OVEN REQUIRES AN EXHAUST FAN WITH NO HOOD. |