Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/21/2014 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* |
| 03/21/2014 |
MECHANICAL - FINAL |
|
Approved |
WILL CHECK GREASE RECEPTORS AT HOODS & PAINT ON EXPOSED DUCTS AT BUILDING FINAL |
| 03/12/2014 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 03/12/2014 |
MECHANICAL - FINAL |
|
Partial Approval |
HOODS, FANS, & DUCTS UP TO ROOF ARE ALL TYPE I. THE DUCTS ON ROOF CONNECTING FAN TO GREASE DUCT ARE NOT TYPE I & ARE NOT WELDED. THE CLEANOUT ACCESS IS NOT TYPE I. PROVIDE HINGE KITS ON 2 FANS & GREASE RECEPTORS. EXTEND DISCHARGE ON SMALL FAN ABOVE MAKEUP AIR UNIT & PARAPET WALL. GAS BAKERY OVEN REQUIRES A TYPE II HOOD. ELEC BAKERY OVEN REQUIRES AN EXHAUST FAN WITH NO HOOD. |