Permit: T13OT01147

Parcel: 11012094D


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: SIGN SITE REVIEW

Permit Number - T13OT01147

Inspection Description - SIGN SITE REVIEW

Inspection Status - Approved

Date Description Inspector Results Comments
11/12/2013 SIGN SITE REVIEW Approved Revised calcs received, stamped & sealed. Structural approved.
11/08/2013 SIGN SITE REVIEW Correction Required Regarding revised documents received 10/29, 11/4 & 11/6 by email

Review per Structural (Eric Newcomb)
1) Engineered calculations need to be stamped and signed by the engineer of record.
2) Once above provided, structural can approve the proposal.

MEETS SIGN VARIANCE CASE S-00-05
ENGINEERING APPROVED FOR S.V.T. ON SITE PLAN.
10/23/2013 SIGN SITE REVIEW Correction Required T13OT01147

10/23 - CUMULATIVE REVIEW OF ITEMS RECEIVED SINCE SUBMITTAL, AND INSPECTION DONE 10/16. THE FOLLOWING CODES ARE REFERENCED: SIGN CODE, NATIONAL ELECTIC CODE, INTERNATIONAL BUILDING CODE. THE PROJECT IS SUBJECT TO SIGN VARIANCE CASE S-00-05.


Sign Code Review: (Heather Thrall) Heather.Thrall@tucsonaz.gov

1) Acknowledged received a location map and revised site plans since submittal. Per 3-18 of the Sign Code, Provide site plan to a measurable scale (a close up view) of the area of the sign installation - show the proposed sign location with setbacks from face of each street curb, with sight visibility triangle.
2) Per inspection 10/16, there is a 10.5" difference between grade at base of the sign and the adjacent top of street curb. Per 3-33 of the Sign Code & Sign Code Administrator's ruling, sign height is measured from top of street curb for signsin within 40' of a roadway. Provide elevation drawing view showing height difference between grades and note the height from both the base of the sign and from the top of curb. Max sign height is allowed at 12' per variance S-00-05.

N.E.C. (Eric Newcomb)

1) Acknowledged the symbol for a shut off switch is shown on the plan, but no shut off switch location is indicated. Indicate number of circuits.

IBC/Structural Review: (Eric Newcomb)

1). Provide engineer's sealed drawing on one sheet - not separated into two sheets.
2) Provide engineer's calculations to support the sealed drawing.
3) Footer shown on color elevation rendering does not match engineer's drawing.
10/16/2013 SIGN SITE REVIEW Correction Required 10.5" difference in grade between base of sign and top of adjacent street curbs. Revise elevation plan to show this grade difference, as sign height is measured from top of street curb. Max height is 12' per variance case.
10/07/2013 SIGN SITE REVIEW Continued Received additional revised site plan. Review continues, with engineering staff assisting drafter to draw sight visibility triangles correctly.
10/02/2013 SIGN SITE REVIEW Continued Received revised site plan. Review continues
09/26/2013 SIGN SITE REVIEW Continued Continuing to receive revised and additional documents from contractor.