Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T13OT00339
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/24/2013 | FIRE - FINAL | Approved | ||
03/28/2013 | FIRE - FINAL | Denied | 1. Exit signs needed above all 3 exits. 2. Illuminated exit signs needed. 3. Emergency light needed throughout warehouse. 4. Ceiling tiles that are damaged need to be replaced. 5. Fire extinguishers need service. 6. Need copy of annual sprinkler report. 7. All electrical wiring needs to be covered. 8. Damaged walls in warehouse need to be repaired. 9. Broken electrical outlets need to be repaired. 10. Escutcheons needed on sprinkler heads. 11. Suite numbers needed. |
|
03/27/2013 | FIRE - FINAL | Denied | 1. Doors locked at 2:20pm |