Permit: T13OT00241

Parcel: 11201014N

Inspection Status: Approved

Inspection History: CERTIFICATE OF OCCUPANCY

Date Description Inspector Results Comments
03/06/2013 CERTIFICATE OF OCCUPANCY Approved PER SIGNED JOB CARD
03/04/2013 CERTIFICATE OF OCCUPANCY Not ready for Inspection 1. Correct the address. Remove 3843, and post unit numbers 01, and 02. Water heater replaced without permit. No flex allowed on the T&P relief drain. Water heater not rated for exterior installation. (require enclosure). Armaflex not installed per manufacturers specifications. No UV protection. Remove metal tape from electrical connection.. Washer requires hammer arrestors. Stove requires anti-tip. May not be a complete list.