Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/28/2014 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/14/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/14/2014 | MECHANICAL - FINAL | Denied | 1. BUSHING REQUIRED AT DISCONNECT 2. DOUBLE LUGGING AT TERMINALS NOT PERMITTED 3. WHITE WIRE NOT APPROVED AS HOT LEG 4. SUPPLY DUCT JOINTS NOT SEALED 5. INDOOR UNIT DATA PLATE NOT IDENTIFIED 6. DEAD FRONT MISSING FROM INDOOR DISCONNECT |