Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T13ME00002
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/29/2013 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
01/17/2013 | MECHANICAL - FINAL | Denied | CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. A/C UNIT OVERFUSED 45 AMP IS MAX 50 AMP BREAKER NOT ADEQUATE FOR A/C UNIT & HEAT STRIP COMBINED. ATTACH A PERMANENT LABEL FOR HEAT STRIP |