Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2013 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/06/2013 | ELECTRIC - SERVICE UPGRADE | Denied | NO WORK PROGRESS | |
| 05/06/2013 | ELECTRIC - SERVICE UPGRADE | Denied | *LUL AT SERVICE NOT TO CODE 250.8 & 250.13 ALSO NOT NEEDED A REINSPECTION FEE MAY BE ASSESSED |
|
| 05/01/2013 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 04/29/2013 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 04/29/2013 | ELECTRIC - SERVICE UPGRADE | Denied | 1) ADDRESS LABEL PANELS 2) LABEL ALL BREAKERS 3) SUPPORT CONDUIT ON SIDE OF PANEL AND BELOW SERVICE 4) ONLY ONE GROUNDING ELECTRODE CONDUCTOR PER TERMINAL LUG 5) TIGHTEN LOOSE FITTINGS 6) PROTECT CONDUCTOR IN jUNCTION BOX 300.4, 356.42 7) BOND JUNCTION BOX ( 2547) 8) NEED GROUNDING ELECTRODE SYSTEM AT 2ND STRUCTURE 250.32 9) NEED MANUFACTURES HOLD DOWN MAIN BREAKER 408.36 (D) |
|
| 04/23/2013 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 04/23/2013 | ELECTRIC - SERVICE UPGRADE | Partial Approval | 1. LINE SIDE ONLY 2. RECALL FOR LOAD SIDE INSPECTION |