Permit: T13EL00085

Parcel: 111084100


Addresses:

2547 N WINSTEL BL

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/08/2013 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
05/06/2013 ELECTRIC - SERVICE UPGRADE Denied NO WORK PROGRESS
05/06/2013 ELECTRIC - SERVICE UPGRADE Denied *LUL AT SERVICE NOT TO CODE 250.8 & 250.13
ALSO NOT NEEDED
A REINSPECTION FEE MAY BE ASSESSED
05/01/2013 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
04/29/2013 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
04/29/2013 ELECTRIC - SERVICE UPGRADE Denied 1) ADDRESS LABEL PANELS
2) LABEL ALL BREAKERS
3) SUPPORT CONDUIT ON SIDE OF PANEL AND BELOW SERVICE
4) ONLY ONE GROUNDING ELECTRODE CONDUCTOR PER TERMINAL LUG
5) TIGHTEN LOOSE FITTINGS
6) PROTECT CONDUCTOR IN jUNCTION BOX 300.4, 356.42
7) BOND JUNCTION BOX ( 2547)
8) NEED GROUNDING ELECTRODE SYSTEM AT 2ND STRUCTURE 250.32
9) NEED MANUFACTURES HOLD DOWN MAIN BREAKER 408.36 (D)
04/23/2013 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
04/23/2013 ELECTRIC - SERVICE UPGRADE Partial Approval 1. LINE SIDE ONLY
2. RECALL FOR LOAD SIDE INSPECTION