Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2013 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 04/26/2013 | ELECTRIC - SERVICE UPGRADE | Denied | 1) POST ADDRESS ON BUILDING 2) MAINTAIN WORKING SPACE AT SUB PANEL 3) LABEL ALL CIRCUIT BREAKERS PER 408.4 4) CLEAN SURFACE UNDERGROUND BAR 5) FULL TERMINATE STRANDED CONDUCTOR 6) DRYWALL SCREWS NOT APPROVED MOUNTING HARDWARE 7) USE APPROVED FITTING WITH LB 8)RECEPTACLE COVER TO BE WEATHER PROOF WEATHER OR NOT PLUGGED INTO 406.8 9) PROPERLY TERMINATE SEAL TITE FITTING |
|
| 04/12/2013 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* |