11/25/2013 INSP - INITIAL CODE ENFORCMENT Approved MOBILE HOME PARK VIOLATIONS

THERE IS A 400 AMP MASTER METERED SYSTEM WITH TWO 200 AMP SAFETY SWITCHES ADJACENT TO THE METER LOCATION. THERE IS ALSO A IS PANEL BOARD AND AN ABANDON 4 GANG JUNCTION BOX IN THE SAME LOCATION.

1. NO LABELING ON THE SAFETY SWITCHES

2. THE 4 GANG J-BOX IS NOT RATED FOR OUTDOOR

3. NO LABELING ON THE PANEL BOARD

4. SAFETY SWITCHES ARE NOT PROPERLY MOUNTED TO THE BACKER BOARD


UNIT 1

1.PEDESTAL OK

2.GAS LINE NOT PROPERLY SECURED, EXCESSIVE MOVEMENT ON PIPING UNDER THE MOBILE HOME.

3.PROPERTY; CARPET ON THE GROUND AND TRASH & DEBRIS


UNIT 2

1.PEDESTAL OK

2.GAS LINE NOT PROPERLY SECURED, EXCESSIVE MOVEMENT ON PIPING UNDER THE MOBILE HOME.

3.PROPERTY; CARPET ON THE GROUND

UNIT 3

1.PEDESTAL OK

2.RV LIFE LINE HAS SPICES

3.CORD CAP HAS SINGLE GANG INTERIOR JUNCTION BOX TO THE RV ADAPTER / LIFE LINE.

4.PROPERTY; TORN CARPET ON THE GROUND, TORN SOFA, LITTER.

UNIT 4

1.PEDESTAL OK

2.CORD CAP IS DAMAGED ( MUST BE REPLACED )

3.GAS LINE NOT PROPERLY SECURED, EXCESSIVE MOVEMENT ON PIPING UNDER THE MOBILE HOME.

4.PROPERTY; CARPET ON THE GROUND, TRASH AND DEBRIS.

5.EXPOSED PVC WATER SUPPLY LINE

UNIT 5

1.PEDESTAL HAS CORD TYPE LIFE LINE HARD WIRED

2.THE MAIN BREAKER IS A 30 AMP SINGLE POLE TYPE NO T HANDLE

3.PROPERTY; ANIMAL WASTE

UNIT 6

1.THE MAIN BREAKER IS A 30 AMP SINGLE POLE TYPE NO T HANDLE

2.PROPERTY; ANIMAL WASTE

3.WATER LEAKS AT THE SUPPLY LINE.

UNIT 7

1. PEDESTAL OK.

UNIT 8

1.PEDESTAL HAS CORD TYPE LIFE LINE HARD WIRED

2.DEAD FRONT UNSECURED

3.USED OPENING NEXT TO SINGLE POLE 30 AMP BREAKER

4.GAS LINE NOT PROPERLY SECURED, EXCESSIVE MOVEMENT ON PIPING UNDER THE MOBILE HOME.

UNIT 9

1.PEDESTAL OK

2.PROPERTY; TRASH AND DEBRIS

UNIT 10

1.DEAD FRONT MISSING

2.PVC CONDUIT NOT PROPERLY INSTALLED WITH WATER CONNECTOR FITTING.

3.PROPERTY HAS TRASH AND DEBRIS

4.THIS UNIT IS VACANT WITH BROKEN WINDOWS, LOOK ABANDON.

UNIT 11

1.PVC CONDUIT NOT PROPERLY INSTALLED

2.OVER CURRENT PROTECTION IS 60 AMPS

3.UNUSED OPENING, MISSING RECEPTACLE

4.GAS LINE NOT PROPERLY SECURED, EXCESSIVE MOVEMENT ON PIPING UNDER THE MOBILE HOME.

5.THIS UNIT IS VACANT ABANDON AND UNSECURED WITH A DILAPIDATED ATTACHED PORCH.

UNIT 12

1.MAIN BREAKER NOT PROPERLY SEATED

2.GAS LINE NOT PROPERLY SECURED, EXCESSIVE MOVEMENT ON PIPING UNDER THE MOBILE HOME.

UNIT 13

1.PEDESTAL HAS CORD TYPE LIFE LINE HARD WIRED

2.GAS LINE NOT PROPERLY SECURED, EXCESSIVE MOVEMENT ON PIPING UNDER THE MOBILE HOME.


UNIT 14

1.THERE IS ONE UNUSED OPENING AT THE MAIN BREAKER COVER LOCATED WITHIN THE PEDESTAL. THE UNIT HAS ONE SINGLE POLE 30 AMP BREAKER.
2.GAS LINE NOT PROPERLY SECURED, EXCESSIVE MOVEMENT ON PIPING UNDER THE MOBILE HOME

UNIT 15

1.PEDESTAL HAS CORD TYPE LIFE LINE HARD WIRED

2.DEAD FRONT IS NOT SECURED

3.THE OVER CURRENT PROTECTION MAIN BREAKER IS 100 AMPS, THE LIFE LINE IS 50 AMPS.

4.GAS LINE NOT PROPERLY SECURED, EXCESSIVE MOVEMENT ON PIPING UNDER THE MOBILE HOME

UNIT 16

1.THERE IS ONE UNUSED OPENING AT THE MAIN BREAKER COVER LOCATED WITHIN THE PEDESTAL. THE UNIT HAS ONE SINGLE POLE 30 AMP BREAKER.

UNIT 17

1.METER AT PEDESTAL IS BLANKED OFF

UNIT 18

1.PEDESTAL HAS CONDUIT WHICH RUNS UNDER GROUND AND RISES UP ADJACENT TO THE MOBILE HOME TO A RADIATOR HOSE WHICH IS ACTING AS A CONNECTOR TO A JUNCTION BOX.

2.THE PEDESTAL BREAKERS NOT MARKED. THERE IS A 200 AMP AND A 50 AMP.

UNIT 19

1.METER AT PEDESTAL IS BLANKED OFF

UNIT 20

1.OK

UNIT 21

1.THIS IS A SMALL BLOCK BUILDING WITH A SMALL MOBILE HOME ATTACHED. THE ARIEL'S SHOW THIS CONFIGURATION SINCE 1998.
2.GAS WATER HEATER HAS DRAIN VALVE THAT LEAKS
3.GAS WATER HEATER HAS VENT PIPE NOT PROPERLY ATTACHED
4.GAS WATER HEATER COMPARTMENT HAS MISSING DOOR
5.EXTERIOR JUNCTION BOX HAS MISSING COVER PLATE
6.SMALL ATTACHED AWNING IS DILAPIDATED

LAUNDRY ROOM / BUILDING

1.MAIN DISCONNECT HAS NO LABELING.
2.UNSECURED DEAD FRONT
3.UNUSED OPENING AT BOTTOM OF DISCONNECT
4.30 AMP CIRCUIT BREAKER HAS 12 GAUGE WIRE
5.THE BUILDING HAS DEEP CRACKS IN THE MORTAR JOINTS
6.ALL OF THE WOOD HEADERS ALL SEVERELY DETERIORATED
7.TWO DAMAGED WINDOW OPENINGS