Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T13DV08530

Parcel: 140132660


Addresses:

2201 E PINE ST

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
11/15/2013 INSP - INITIAL CODE ENFORCMENT Approved VISITED SITE, MET WITH TFD INVESTIGATORS, WHO METIONED THEY HAD ALSO JUST ARRIVED, WERE UNABLE TO MEET WITH FIREFIGHTERS WHO HAD ALREADY CLEARED THE SITE UPON THEIR ARRIVAL. MET WITH OWNER JESSE REYES, DSD EMPLOYEE, METIONED FIRE STARTED IN THE FAN AND MOVED INTO THE CEILING OF THE BATHROOM. THERE WAS A SMOKE DETECTOR ACROSS THE HALL FROM THE BATHROOM BUT IT DID NOT GO OFF. FIRE DID BURN A COUPLE OF RAFTERS OF THE CEILING AND SOME FRAMING FOR A SOFFIT DIRECTLY BEHIND THE BATHROOM WALL. WIRING IN THE SOFFIT, SEVERAL WIRES ALSO MELTED, PLUMBING IN THE PLUMBING WALL ALSO MELTED, AND DRYWALL DAMAGED. CHECKED THE MAIN SERVICE PANEL AFTER OWNER ASKED IF HE WOULD BE ABLE TO STAY IN THE HOUSE BUT INSPECTION OF THE PANEL FOUND MIXED BREAKERS, LOOSE BREAKERS, DOUBLE-TRIPLE LUGGING, BURNED WIRING, TERMINATED WIRES WITH NO WIRE NUTS. DUE TO THE MULTIPLE ISSUES I DETERMINED THE PANEL COULD NOT BE REENERGIZED.
OWNER DID DECIDE TO STAY WITH HIS MOM WHO LIVES ON THE SAME STREET. NOV EMERGENCY VACATE WAS ISSUED AND NOV FOR DAMAGE ISSUES AND PERMITS ALSO ISSUED. DAMAGE REPORT IN SIRE. PICTURES WERE TAKEN.