Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date |
Description |
Inspector |
Results |
Comments |
| 10/16/2013 |
INSP - INITIAL CODE ENFORCMENT |
|
Approved |
10/16/13 - INITIAL INSPECTION - MET WITH TENANTS IN FIRST STRUCTURE ALLOWED ME TO REAR YARD AND ACCESSORY STRUCTURE // ACCESSORY STRUCTURE HAD BEEN CONVERTED INTO DWELLNG WITH BEDROOM/ KITCHEN SINK AND TOILET ALL SEEN FROM WINDOWS // PER TENANTS WAS NOT OCCUIPED// PLUMBING ALONG 2ND STRUCTURE UNSUPPORTED // POWER TO 2ND UNIT IS BEING SUPPLIED BY 100 AMP PANEL USED TO POWER MAIN STURCTURE WITH NO SEPARATE DISCONNECT // UNMARKED BREAKERS IN PANEL // MIXED MATCH BREAKERS WITH PANEL CALLING FOR GE BREAKERS // DEAD FRONT MISSING // CONDUIT FROM BOTTOM OF PANEL RUNNING ALONG GROUND TO SECOND UNIT TO POWER A/C UNIT // RESEARCH FOUND UTILITY SHED BACK IN 1972 BUT NO RECORD OF PERMITS FOR CONVERSION TO DWELLING OR PERMITS FOR PLUMBING OR ELECTRIC // NOV TO FOLLOW // AV |