Case: T13DV07601

Parcel: 111051660

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T13DV07601

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
10/15/2013 INSP - INITIAL CODE ENFORCMENT Approved MET W/OCCUPANT TOOK R.H. W/ME. OCCUPANT HAD USAFE, NARROW PATHWAYS THROUGHOUT UNIT. STACK OF BOXES AND MISCELLANEOUS ITEMS OVER 5'7". SMOKE DETECTOR REMOVED OFF WALL AND BATTERY REMOVED FROM THE SMOKE DETECTOR, BATHROOM PLUMBING IN SINK LEAKING, NO GFI IN KITCHEN OUTLETS, DOUBLE LUGGING IN ELECTRICAL DISCONNECT BOX #3427. GROUND AND NEUTRAL NEEDS TO BE SEPERATED AND BOX NEEDS TO BE LABELED. LIGHTING SYS IS ON A 100 AMP FUSE W/A 30 AMP WIRE.