Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
Case Number - T13DV04887
Inspection Description - INSP - FOLLOW UP CODE ENFORCE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/12/2014 | INSP - FOLLOW UP CODE ENFORCE | Approved | Visited site. most items on the previous inspection report have been completed. Will return later today. | |
05/12/2014 | INSP - FOLLOW UP CODE ENFORCE | Approved | All items on inspection report have been completed. MOVE TO CLOSE OUT | |
04/28/2014 | INSP - FOLLOW UP CODE ENFORCE | Denied | 1.Grounding electrode conductor to terminate at grounded terminal. 2.Can not use sheet metal screws for grounding. 3.New receptacle to be weatherproof at west patio. 4.Extension cord can not pass through the partition. 5.Maintain working clearance at subpanel. 6.Finish NM Cable and L.B. at subpanel. 7.Missing receptacle covers at subpanel and the ceiling in the pool room. 8.Dishwasher receptacle to be for a wet location. 9.Exhaust fan in the women's restroom exposed and not functionally working. 10.Receptacle and plate by the north wall soffit in the bar detached. FINISH 05/12/14 |
|
03/27/2014 | INSP - FOLLOW UP CODE ENFORCE | Approved | 03/27/14 - ON SITE WITH R. HOLLANDER MET WITH ELECTRICIAN OWNER OF BOB DOBBS AND MANAGER // ALL GIVEN A COPY OF NOV AND WALKED THEM THEM THRU ENTIRE NOTICE // CONTRACTOR UNDERSTOOD WHAT NEEDED TO BE DONE // NUMBERS EXCHANGED // WILL F/U IN 20 DAYS // AV | |
02/27/2014 | INSP - FOLLOW UP CODE ENFORCE | Approved | Meet with propery manager and maintance man to go over the items for the outside of the building. gave them a copy of the NOV and pictures. | |
12/10/2013 | INSP - FOLLOW UP CODE ENFORCE | Approved | Visited site and took pictures. There has been no progress of work since the temporary work was done the day after the fire. |