Case: T13DV04786

Parcel: 107111710


Addresses:

212 W BLACKLIDGE DR


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T13DV04786

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
07/01/2013 INSP - INITIAL CODE ENFORCMENT Approved Service disconnect has sever deterioration at grounded/neutral terminal. This is due to loose connections causing heat damage to the conductor and insulation. There is also corrosion to the point of causing metal failure to the terminal. The spice connector has not been installed to manufactures instructions. ther are too many conductors in the connector. The srevice disconnects are located over the gas piping and meters. It is noted that there is additional electrical added on the exterior of the unit.