Case: T13DV04231

Parcel: 11304148A


Addresses:

3230 N 1ST AV


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T13DV04231

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
06/18/2013 INSP - INITIAL CODE ENFORCMENT Approved FIRE CALL OUT: CALLED OWNER MRS ONG. (VOICE-MAIL)
NORTH SIDE OF STRIP MALL (REAR) FIRE STARTED IN SMALL EXTERIOR ROOM. MATTRESSES, PAPER PRODUCTS. EFFECTED ELECTRICAL SYSTEM TO ALL PARKING LOT LIGHTS, POLE LIGHTING, CANOPY LIGHTING. 2" PIPE CARRYING ELECTRICAL CONDUCTORS INSIDE BURNT, MELTED, AT BOTTOM WHERE 90 BEND WIRES BURNT BARE, SHORTED OTHER SERVICE PANEL EFFECTING 1 RENTER MIA CLOTHING, NO ELECTRICAL SERVICE, LIGHTING/COOLING.
ON SITE: 2 SUPERVISIORS, RICK, MARTIN.
ELECTRICAL CONTRACTOR SABINO ELECTRIC (MONTE) WAS CONTACTED BY FOOD CITY. WAS EVALUATING SERVICE CONNECTED TO FOOD CITY.
ALL PARKING LOT LIGHTS, POLE LIGHTS, SECURITY LIGHTS.
AT THIS TIME SABINO ELECTRIC DE-ENERGIZED ALL PANELS FROM MAIN SERVICE PER CONVERSATION HE IS ONLY TO BE LOOKING AT FOOD CITY ELECTRICAL, NOT REST OF SERVICE.
PALO VERDE ELECTRIC SHOWED ON SITE: (RICK) RICK WAS CALLED BY FAMILY DOLLAR STORE. RICK WAS TO EVALUATE ONLY FAMILY DOLLAR STORE ELECTRIC.
WHILE ON SITE SPENT TIME WITH INSPECTORS AND LOOKED AT ALL OTHER ISSUES, HAZARDS. CAN NOT WORK ON ISSUES UNTIL OWNER RETAINS HIS COMPANY.
TRYING TO MAKE CONTACT WITH OWNER MIA CLOTHING STORE STATED WAS ON VACATION. CRUISE (MEDITERRANEAN)
MIA DID GET TO MAKE CONTACT WITH OWNER, OWNER RETURNED INSP. CALL. WENT OVER ISSUES OF FIRE, FIRE DAMAGE. MIA TOTALLY OUT OF ELECTRICAL SERVICE. ALL OTHER DAMAGE FIRE CREATED. OWNER STATED WILL CALL CONTRACTOR DUFFY ELECTRIC. (STEVE) SHE WORK WITH PRIOR. TALKED WITH STEVE, STEVE SHOWED ON SIGHT WENT OVER ALL ISSUES, BEFORE HE CAN START ANY WORK HAS TO BE APPROVED BY OWNER. (ON VAC.) OWNER CALL BACK AGAIN AND HAD INSP. CALL ANOTHER PERSON (GARY) BELIEVES AND TRUST GARY, MET WITH GARY ON SITE, WENT OVER ISSUES, GARY AGREES TO PROBLEMS AND HAZARDS,
GAME PLAN: GET TEMP. POWER PERMIT REDO ELECTRIC TO MIA CLOTHING STORE (UNDER PERMIT) NOT TO RE-ENERGIZE IF DE-ENERGIZED AT THIS TIME. ABATE OTHER HAZARDS, DISCARD IF NOT IN USE GET RID OF. HAS A GOOD PLAN.
DIFFICULTIES: OWNER ON CRUISE (MEDITERRANEAN) NOT EASLY CONTACTED. NEEDS TO BE INVOLVED, PAYIOR, GARY WILL TRY TO KEEP UP DATED ON PROGRESS, SMALL PROGRESS, MOSTLY LOOKING AT WAITING UNTIL OWNER RETURNS. RETURNS JULY 9TH. APPROX 3 WEEKS.
WILL GO OVER ISSUES AGAIN WITH BOTH SUPERVISORS AFTER MEETING WITH GARY.
ELECTRICAL ISSUES OBSERVED;
719 E. Fort Lowell
The fires at the rear of the property caused sever damage to the conduits and conductors in the raceways that were in the path of the fire or close proximity. An 8x8x6 junction box appears to have heat related damage also, with the photo cells below the box, melted away. The small outdoor junction box feeding from the ¾" conduit also appears heat damaged. At the service location there are three disconnecting means inside the covering enclosure. The center disconnecting means cover can not be opened fully to access or work on. The cover for the contactor box was not properly secured to the box. The controlling circuit was disconnected. The right disconnecting means was energized, but marked "Abandoned" with partial removal of conductors and circuits connecting to other electrical boxes. The cover for the contactor box was not properly secured to the box. The left disconnecting means feed the panel with circuits labeled for Pole lights, Canopy lights, and other lighting. None of the disconnecting means were labeled as to the usage or supply. It is noted that all of the disconnecting means including the service main are in a moderate to severe deteriorated condition with unused openings. At the service location several junction boxes containing contactors may have not been code compliant at the time of install were also noted that

713 E Fort Lowell
The feeder conduit for this space passed through the fire area. The conduit was separated at emergence from the ground. The conductors had the insulation burned from the wire exposing them to the conduit causing a ground fault condition and blowing all three (3) fuses. The entire raceway was severely heat damaged. The service disconnecting means is attached to a weather rotted board that is detaching from the wall. The condition of the service disconnecting means is deteriorated with build-up of foreign material and dirt. The neutral termination has multiple tap connections. The main service gutter/raceway is severely deteriorated with openings through the abandoned electrical equipment allowing access for birds or persons to contact unprotected service entrance conductors. From this gutter/raceway a 4" conduit feeds to another service gutter at different location (Mixed Martial Arts and the Barber shop). This will be addressed under 701 E. Fort Lowell. There is no labeling of the disconnecting means as to property served or usage.

701 E. Fort Lowell
This service is being feed from another location's TEP service drop. It is not grouped with the other services for first responder to affectively disconnect as necessary under an emergency condition. There was no labeling present as to property served, to conditions, or usage. The service disconnect for 701 E. Fort Lowell has multiple tap connections on the line side of the service disconnect. It appears that the two other service disconnects are being feed from these taps. The terminal lug were not intended for more that one conductor. This disconnect has sever deterioration leaving portions of the enclosure open to the environment due to rusted out metal. This service disconnecting means also has build-up of foreign material and dirt. The service nipple connection is rusted to the point of loss of effective ground fault path for safe operation. The main service gutter/raceway is severely deteriorated with unused openings. It is noted that all of the additional disconnecting means are in a moderate to severe deteriorated condition with unused openings.