Addresses:

3508 S 8TH AV


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T13DV03514

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
05/23/2013 INSP - INITIAL CODE ENFORCMENT Approved ELECTRICAL VIOLATIONS

THERE IS A 400 AMP MASTER METERED SYSTEM WITH TWO 200 AMP PANELS ADJACENT TO THE METER LOCATION.

1. GROUNDING ELECTRODE CONDUCTOR SYSTEM IS INSTALLED CODE COMPLIANT

2. WORKING CLEARANCE IN FRONT OF SERVICE EQUIPMENT DOES NOT HAVE THE REQUIRED 36 INCHES WORKING SPACE

3. NO LABELING ON SERVICE EQUIPMENT

4. FILL UN USED OPENINGS IN THE PANEL

5. BROKEN PANEL COVER ON THE NORTH PANEL

6. MULTIPLE NEUTRALS CONDUCTORS PLACED UNDER THE SAME SCREW TERMINAL IN THE INTERIOR OF THE NORTH PANEL

7. EXPOSED AND DETERIORATED NON METALLIC SHEATHED CABLE FEEDING THE OVERHEAD LIGHT.

8. UNAPPROVED WIRING METHODS

UNIT 1
NO DISCONNECT EQUIPMENT (NO PANEL W/ BREAKERS)
NO CONDUCTOR PROTECTION
DETERIORATED NONMETALLIC SHEATHED CABLE BEING USED AS A LIFE LINE
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR.
NO GROUNDING ELECTRODE SYSTEM
UNAPPROVED WIRING METHODS
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
LIFE LINE NOT CODE COMPLIANT
Water Heater- vent too low, no enclosure, copper used for gas line
ABS is exposed, improper clean out connection


UNIT 2
HARD WIRED LIFELINE (LIFE LINE NOT CODE COMPLIANT)
NO GROUNDING ELECTRODE SYSTEM
IMPROPER BREAKER FOR 220 RECEPTACLE MISSING HANDLE TIE OR REPLACE WITH TWO POLE TYPE
NO LABELING
Water Heater- vent too low, no enclosure, needs relief valve discharge pipe.
copper used for gas line , ABS is exposed, improper clean out connection.


UNIT 3
WORKING CLEARANCE
SUPPORT POST IS DETERIORATED
NO GROUNDING ELECTRODE SYSTEM
NO LABELING
Water Heater- vent too low, no enclosure, needs relief valve discharge pipe.
copper used for gas line , ABS is exposed, improper clean out connection.


UNIT 4
WORKING CLEARANCE
LIFE LINE NOT CODE COMPLIANT
NO GROUNDING ELECTRODE SYSTEM
SUPPORT POST IS DETERIORATED
NO LABELING
Water Heater- no enclosure, ABS exposed, improper clean out connection.

UNIT 5
NO GROUNDING ELECTRODE SYSTEM
SUPPORT POST IS DETERIORATED WITH TERMITE DAMAGE
WORKING CLEARANCE
NO DEAD FRONT
LIFE LINE NOT CODE COMPLIANT
UNAPPROVED WIRING METHODS
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
Water Heater- no vent pipe ,no enclosure, needs relief valve discharge pipe, improper clean out connection.
UNIT 6
NO GROUNDING ELECTRODE SYSTEM
WORKING CLEARANCE
LIFE LINE NOT CODE COMPLIANT
DETERIORATED NONMETALLIC SHEATHED CABLE BEING USED AS A LIFE LINE
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
LACK OF A FILLER PLATE IN DEAD FRONT
UNAPPROVED WIRING METHODS
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
Water Heater-OK, ABS exposed, improper clean out connection.
8 x 10 addition

UNIT 7
NO GROUNDING ELECTRODE SYSTEM
WORKING CLEARANCE
FILL UN USED OPEN SPACES
USING PVC WATER CONNECTORS IN CONDUIT
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR.
UNAPPROVED WIRING METHODS
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
LIFE LINE NOT CODE COMPLIANT
Water Heater- no vent pipe ,no enclosure,
ABS pipe needs paint


UNIT 8
30 AMP DISCONNECT HAS INTERNAL PARTS THAT ARE DETERIORATED AND HAVE RUST
NO GROUNDING ELECTRODE SYSTEM
WORKING CLEARANCE, VEGETATION OF RAZOR WIRE ADJACENT TO SYSTEM
LIFE LINE NOT CODE COMPLIANT
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR UNAPPROVED WIRING METHOD
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
Water Heater- no enclosure, improper clean out connection.
ABS pipe needs paint

UTILITY ROOM / LAUNDRY ROOM
TWO WASHERS AND TWO DRYERS ARE OUT DOOR AND EQUIPMENT IS NOT RATED FOR OUTDOOR USE.
60 AMP SERVICE IS UN ACCESSIBLE SODA MACHINES IS BLOCKING ACCESS.
WORKING CLEARANCE
UNPROTECTED RECEPTACLE BOX (NOT RATED FOR OUTDOOR USE)

REAR OF UTILITY ROOM HAS 100 AMP PANEL.
THE NEUTRALS ARE BONDED TO THE HOUSING.( NEUTRALS MUST BE ISOLATED)
NO GROUNDING ELECTRODE SYSTEM
NO LABELING
FILL USED OPENINGS
THIS PANEL BOARD IS NOT SUITABLE FOR APPLICATION
NO LABELING

OFFICE / TRAILER
PEDESTAL HAS ONE PANEL BOARD AND TWO HM DISCONNECTS
NO GROUNDING ELECTRODE SYSTEM
WORKING CLEARANCE
SUPPORT POST IS DETERIORATED
NONMETALLIC SHEATHED CABLE USE OUTDOOR AND IS DETERIORATED
RECEPTACLE BOX (NOT RATED FOR OUTDOOR USE)
UNAPPROVED WIRING METHODS
NO LABELING

UNIT 9
FILL UN USED OPENINGS
EXPOSED NONMETALLIC SHEATHED CABLE
NO GROUNDING ELECTRODE SYSTEM
DISCONNECT HAS OPEN HOLE
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
UNAPPROVED WIRING METHODS
SUPPORT CONCRETE BASE CRACKED
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
LIFE LINE NOT CODE COMPLIANT
Water Heater-no enclosure, needs relief valve discharge pipe. improper clean out connection.
Storage issues.

UNIT 10
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
GROUNDING ELECTRODE SYSTEM NOT INSTALLED CORRECTLY
INTERNAL PARTS OF THE DISCONNECT ARE DETERIORATED
UNAPPROVED WIRING METHOD (3 METERS ARE FEED BY ONE MULTIPLE LUG AT THE OVER HEAD LOCATION. (NO WEATHER HEAD PER DISCONNECT)
SUPPORT CONCRETE BASE CRACKED
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
LIFE LINE NOT CODE COMPLIANT
improper clean out connection. ABS pipe needs paint

UNIT C
ALL CONDUCTORS ARE WHITE
NO GROUNDING ELECTRODE SYSTEM
UNAPPROVED WIRING METHODS
RECEPTACLE NOT INSTALLED CODE COMPLIANT PER ENVIRONMENT
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
SUPPORT CONCRETE BASE CRACKED
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
LIFE LINE NOT CODE COMPLIANT
improper clean out connection.

UNIT 11
OVERHEAD FEEDERS NOT TO CODE HEIGHT
DETERIORATED EXPOSED NONMETALLIC SHEATHED CABLE
UNAPPROVED WIRING METHODS
SUPPORT POST IS DETERIORATED
DETERIORATED NONMETALLIC SHEATHED CABLE BEING USED AS A LIFE LINE
NO GROUNDING ELECTRODE SYSTEM
JUMPER WIRE INSTALLED IN THE TWO POLE BREAKER (DISCONNECT NOT INSTALLED PER MANUFACTURES INSTRUCTIONS.
THIS PANEL BOARD IS NOT SUITABLE FOR APPLICATION
SUPPORT POST IS DETERIORATED
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
LIFE LINE NOT CODE COMPLIANT
improper clean out connection. ABS pipe needs paint
UNIT 12
IMPROPER DISCONNECT HEIGHT
LIFE LINE HARD WIRED (LIFE LINE NOT CODE COMPLIANT)
DETERIORATED EXPOSED NONMETALLIC SHEATHED CABLE
UNAPPROVED WIRING METHODS
NO GROUNDING ELECTRODE SYSTEM
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
IMPROPER JUNCTION BOX
BACKER BOARD LOOSE
WORKING CLEARANCE
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
storage, debris issues, water heater- copper used for gas line. improper clean out connection.

UNIT B
30 AMP DISCONNECT HAS JUMPER BACK FEEDING
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
NO GROUNDING ELECTRODE SYSTEM
UNAPPROVED WIRING METHODS
DETERIORATED EXPOSED NONMETALLIC SHEATHED CABLE
SUPPORT POST IS DETERIORATED
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
LIFE LINE NOT CODE COMPLIANT
improper clean out connection.

UNIT 14
NO GROUNDING ELECTRODE SYSTEM
METAL RACEWAY POSSIBLY HAS GROUNDING ELECTRODE CONDUCTOR NOT BONDED IF INSTALLED PER CODE.
SUPPORT POST IS DETERIORATED
NO LABELING
Water Heater- no vent pipe, no enclosure, improper clean out connection.
ABS pipe needs paint

UNIT 15
NO GROUNDING ELECTRODE SYSTEM
NO LABELING
ABS sewer pipe needs paint

UNIT 16
NO GROUNDING ELECTRODE SYSTEM
SUPPORT POST IS DETERIORATED
DETERIORATED EXPOSED NONMETALLIC SHEATHED CABLE
WORKING CLEARANCE
IMPROPER CORD CAP
EXPOSE RECEPTACLE OUTLET BOX
NO LABELING
ABS sewer pipe needs paint

UNIT 17
FILL USED OPENINGS
SUPPORT POST IS DETERIORATED
SUPPORT CONCRETE BASE CRACKED
NO GROUNDING ELECTRODE SYSTEM
DETERIORATED EXPOSED NONMETALLIC SHEATHED CABLE
HARD WIRED LIFE LINE (LIFE LINE NOT CODE COMPLIANT)
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
Water Heater- vent too low, no enclosure, copper used for gas line.
improper clean out connection. sewer pipe needs paint

UNIT 18
Water Heater- no enclosure, needs relief valve discharge pipe,
copper used for gas line

SUPPORT POST IS DETERIORATED
SUPPORT CONCRETE BASE CRACKED
NO GROUNDING ELECTRODE SYSTEM
DETERIORATED EXPOSED NONMETALLIC SHEATHED CABLE
HARD WIRED LIFE LINE (LIFE LINE NOT CODE COMPLIANT)
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
FILL USED OPENINGS
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS

UN MARKED DISCONNECT SAME LOCATION AS UNITS 17, 18
60 AMP
SUPPORT POST IS DETERIORATED
SUPPORT CONCRETE BASE CRACKED
NO GROUNDING ELECTRODE SYSTEM
DETERIORATED EXPOSED NONMETALLIC SHEATHED CABLE
HARD WIRED LIFE LINE
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS

WORKSHOP
SUPPORT POST IS DETERIORATED
SUPPORT CONCRETE BASE CRACKED
NO GROUNDING ELECTRODE SYSTEM
EXPOSE RECEPTACLE OUTLET BOX
METAL CONDUIT RACEWAY HAS SEPARATED
RECEPTACLE HAS NO OVER CURRENT PROTECTION
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
UNKNOWN LOCATION OF EQUIPMENT PANEL

UNIT 19
NOT CONNECTED TO DISCONNECT AT POLE.
NOT PROPER GROUNDING ELECTRODE SYSTEM
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
SUPPORT CONCRETE BASE CRACKED
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
LIFE LINE NOT CODE COMPLIANT
vacant
no Water Heater visible.
ABS sewer pipe needs paint,improper clean out connection. TRENCHING IN AREA


UNIT 20
USING PVC WATER FITTING IN RACEWAY
NOT PROPER GROUNDING ELECTRODE SYSTEM
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
SUPPORT CONCRETE BASE CRACKED
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
LIFE LINE NOT CODE COMPLIANT
Water Heater- no enclosure, improper clean out connection.
UNIT 21
CONDEMNED DUE TO DEFECTIVE AND HAZARDOUS DISCONNECT
THE PARK MAINTENANCE DID REMOVE THE DISCONNECT.
THE UNIT WAS VACANT
A VIOLATION NOTICE WAS ISSUED ON SITE
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
NO GROUNDING ELECTRODE SYSTEM
SUPPORT POST IS DETERIORATED
DETERIORATED EXPOSED NONMETALLIC SHEATHED CABLE
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
LIFE LINE NOT CODE COMPLIANT
Water Heater- disconnected, no vent ,no discharge pipe,
ABS sewer pipe needs paint


UNIT 22
30 AMP DISCONNECT HAS INTERNAL PARTS THAT ARE DETERIORATED
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
NO GROUNDING ELECTRODE SYSTEM
SUPPORT POST IS DETERIORATED
DETERIORATED EXPOSED NONMETALLIC SHEATHED CABLE
UNAPPROVED WIRING METHOD (JUMPER WIRE INSTALLED)
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
LIFE LINE NOT CODE COMPLIANT
Water Heater- disconnected, cleanout has vent
sewer pipe needs paint

UNIT 23
30 AMP DISCONNECT HAS INTERNAL PARTS THAT ARE DETERIORATED
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
NO GROUNDING ELECTRODE SYSTEM
SUPPORT POST IS DETERIORATED
DETERIORATED EXPOSED NONMETALLIC SHEATHED CABLE
UNAPPROVED WIRING METHODS JUMPER WIRE INSTALLED
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
LIFE LINE NOT CODE COMPLIANT
Water Heater- vent ok ,no enclosure, needs relief valve discharge pipe
ABS pipe needs paint


UNIT 24
30 AMP DISCONNECT HAS INTERNAL PARTS THAT ARE DETERIORATED
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
NO GROUNDING ELECTRODE SYSTEM
SUPPORT POST IS DETERIORATED
DETERIORATED EXPOSED NONMETALLIC SHEATHED CABLE
UNAPPROVED WIRING METHOD 9 JUMPER WIRE INSTALLED
THIS IS THE DISCONNECT THAT WAS REPLACED BY PARK MAINTENANCE
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
LIFE LINE NOT CODE COMPLIANT
Water Heater- no enclosure, sewer connection needs paint

UNIT 25
NOT PROPER GROUNDING ELECTRODE SYSTEM
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
SUPPORT CONCRETE BASE CRACKED
FILL USED OPENINGS
IMPROPER RISER
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
LIFE LINE NOT CODE COMPLIANT
Water Heater not visible, sewer pipes need paint,small trench in area
UNIT 26
NOT PROPER GROUNDING ELECTRODE SYSTEM
OVERHEAD CONDUCTORS ARE DETERIORATED, NOT RATED FOR OUTDOOR
SUPPORT CONCRETE BASE CRACKED
IMPROPER RISER
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
SEPARATE GROUNDS AND NEUTRALS
NO LABELING
LIFE LINE NOT CODE COMPLIANT
dilapidated ramada attached to unit
improper clean out connection.
UNIT 27
SUPPORT CONCRETE BASE CRACKED
NO GROUNDING ELECTRODE SYSTEM
FILL USED OPENINGS IN DEAD FRONT
NO LABELING
OVERHEAD CONDUCTORS ARE DETERIORATED
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
NO LABELING
LIFE LINE NOT CODE COMPLIANT
ABS pipe needs paint

UNIT 28
SUPPORT CONCRETE BASE CRACKED
NO GROUNDING ELECTRODE SYSTEM
FILL USED OPENINGS IN DEAD FRONT
NO LABELING
OVERHEAD CONDUCTORS ARE DETERIORATED
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
NO LABELING
LIFE LINE NOT CODE COMPLIANT
Water Heater-no enclosure, needs relief valve discharge pipe, copper used for gas line,improper clean out connection.
sewer pipe needs paint, small amount of debris.

UNIT 29
OVERHEAD CONDUCTORS ARE DETERIORATED
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
PROPER LIFE LINE REQUIRED
NO GROUNDING ELECTRODE SYSTEM
NO LABELING
SUPPORT CONCRETE BASE CRACKED
LIFE LINE NOT CODE COMPLIANT
ABS pipe needs paint

UNIT 30
NO GROUNDING ELECTRODE SYSTEM
WORKING CLEARANCE
PROPERLY STRAP RISER
IMPROPER SPLICE CONNECTIONS
OVERHEAD CONDUCTORS ARE DETERIORATED
NO LABELING
SUPPORT CONCRETE BASE CRACKED
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
LIFE LINE NOT CODE COMPLIANT
vacant, no water heater
ABS sewer pipe needs paint


UNIT 31
SUPPORT POST IS DETERIORATED AND CONCRETE BASE CRACKED
NOT SECURED
NO GROUNDING ELECTRODE SYSTEM
OVERHEAD CONDUCTORS ARE DETERIORATED
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
FILL USED OPENINGS
NO LABELING
LIFE LINE NOT CODE COMPLIANT
Water Heater- no enclosure, copper used for gas line, improper clean out connection.
sewer pipe needs paint, Arizona room attached to unit


UNIT 32
CONCRETE BASE CRACKED
NO GROUNDING ELECTRODE SYSTEM
NO LABELING
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
HUB HARDWARE IS NOT CODE COMPLIANT
LIFE LINE NOT CODE COMPLIANT
ABS sewer pipe needs paint, enclosed porch attached to unit

UNIT 33
CONCRETE BASE CRACKED
NO GROUNDING ELECTRODE SYSTEM
NO LABELING
OVERHEAD CONDUCTORS ARE DETERIORATED
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
FILL USED OPENINGS
REPLACE CORD CAP
LIFE LINE NOT CODE COMPLIANT
Water Heater- no vent pipe, no enclosure, copper used for gas line
ABS pipe needs paint, improper clean out connection.


UNIT 34
IMPROPER SPLICE CONNECTIONS TO THE OVERHEAD FEEDERS
SUPPORT POST IS DETERIORATED AND CONCRETE BASE CRACKED
NO GROUNDING ELECTRODE SYSTEM
WORKING CLEARANCE
NO LABELING
OVERHEAD CONDUCTORS ARE DETERIORATED
FILL USED OPENINGS
PROPER LIFE LINE REQUIRED
SECURE RISER
LIFE LINE NOT CODE COMPLIANT
Water Heater- no enclosure, copper used for gas line
ABS pipe needs paint


NOTES:

ALL EXPOSED SEWER CONNECTIONS (ABS) NEED PAINT.
THE OTHER UNITS 4,5,9,A,C,10 HAVE ABS THAT IS NOT VISIBLE.
LIGHT WEEDS,LIGHT TRASH THROUGHOUT PROPERTY,
WITH A FEW EXCEPTIONS.
ONE DEAD TREE.
SOME STORAGE ISSUES.
TRENCHING NEEDS BACKFILLED IN SOME AREAS
3 ADDITIONS ATTACHED TO UNITS
1 DILAPIDATED AWNING.

ZONING VIOLATIONS
THE PLACITA DEL ARROYO RV / RESIDENTIAL TRAILER PARK HAS BEEN EXPANDED TO ACCOMMODATE ADDITIONAL MOBILE HOMES. RESEARCH AT PLANNING AND DEVELOPMENTS SERVICES FOUND A PLOT PLAN WITH 11 MOBILE UNITS, TWO DWELLING UNITS AND A TOOL SHOP/ BATH HOUSE.