Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
Case Number - T13DV03513
Inspection Description - INSP - FOLLOW UP CODE ENFORCE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2013 | INSP - FOLLOW UP CODE ENFORCE | Approved | Units 23-30. Units 27-29 had their electrical service panels daisy-chained together; unit 29 appears to be providing power to both 28 and then 27. Work is not code compliant, potentially hazardous with overloaded circuits, double lugging, and exposed conductors. Owner Mr. Kaplan was notified via phone and email. NOV issued to repair violation under permit with licensed electrician. | |
| 06/03/2013 | INSP - FOLLOW UP CODE ENFORCE | Approved | Units 16-22 (no unit 15) | |
| 05/30/2013 | INSP - FOLLOW UP CODE ENFORCE | Approved | Units 7-14 |