Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date |
Description |
Inspector |
Results |
Comments |
| 01/11/2013 |
INSP - INITIAL CODE ENFORCMENT |
|
Approved |
INSPECTED THE STRUCTURE DUE TO FIRE AT 100 E CONGRESS. INSPECTION FOUND WATER DUMPING OUT OF ELECTRICAL FIXTURES AND MECHANICAL DUCT WORK . FLOORING WAS SATURATED. ROOF MUST HAVE DAMAGE DUE TO THE AMOUNT OF WATER ON THE ROOF AND ENTERING THE STRUCTURE. INTERIOR CEILING SHOWED SIGNS OF POSSILE WATER DAMAGE EVIDENCED BY AREAS OF PEELING PAINT AND PLASTER, AND CRACKING. ELECTRICAL WIRING WAS CUT AT THE WEATHER HEAD DUE TO BURNED WIRES AT THE WEATHERHEAD ENTRANCE. SERVICE PANEL WIRING SHOWED SIGNS OF FIRE DAMAGE. |