Case: T13DV00219

Parcel: 117150050


Addresses:

98 E CONGRESS ST


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T13DV00219

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
01/11/2013 INSP - INITIAL CODE ENFORCMENT Approved INSPECTED THE STRUCTURE DUE TO FIRE AT 100 E CONGRESS. INSPECTION FOUND WATER DUMPING OUT OF ELECTRICAL FIXTURES AND MECHANICAL DUCT WORK . FLOORING WAS SATURATED. ROOF MUST HAVE DAMAGE DUE TO THE AMOUNT OF WATER ON THE ROOF AND ENTERING THE STRUCTURE. INTERIOR CEILING SHOWED SIGNS OF POSSILE WATER DAMAGE EVIDENCED BY AREAS OF PEELING PAINT AND PLASTER, AND CRACKING. ELECTRICAL WIRING WAS CUT AT THE WEATHER HEAD DUE TO BURNED WIRES AT THE WEATHERHEAD ENTRANCE. SERVICE PANEL WIRING SHOWED SIGNS OF FIRE DAMAGE.