Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T13DV00157
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/09/2013 | INSP - INITIAL CODE ENFORCMENT | Approved | VISITED SITE: MET WITH OCCUPANTS. FRONT ENTRY, ENTRY DOOR. ROOM ENCLOSED, NO HEATING OR COOLING TO ROOM. MASTER BEDROOM CONVENIENCE OUTLETS SHOW OPEN GROUND UNDER TEST. BATHROOM GFCI DOES NOT OPERATE. SHOWS REVERSE POLARITY. BATHROOM HAS NOT VENTILATION. TOILET LOOSE AT BASE. KITCHEN LIGHTS UNDER CABINETS HANGING BY WIRING. DINING ROOM CONVENIENCE OUTLETS SHOW OPEN GROUND UNDER TEST. STEP DOWN INTO ADDITION. 100 AMP SERVICE: TREE BLOCKS 3' CLEARANCE FOR SERVICE. NOT LABELED. MIXED BREAKERS, DO NOT SIT IN PANEL PROPERLY. OPEN JUNCTION BOX ABOVE PANEL. OPEN UNSECURE ROMEX IN LAUNDRY ROOM. ADDITION USED AS LIVING ROOM. NO HEAT OR COOLING IN ROOM. BATH OFF LIVING ROOM SHOWS OPEN GROUND UNDER TEST. PATIO ROOF GOES TO ALLEY WALL. (SET BACKS) PATIO SUPPORT POST CUT TOO SHORT, PIECE WEDGED UNDER POST. N/O/V 30 DAYS. |