Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T13CM07742
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/23/2014 | FIRE - FINAL | Approved | ||
09/26/2014 | FIRE - FINAL | Partial Approval | 1. Okay to occupy in the following areas: - 1st floor North and South lobbies. - Interview room corridors. - 1st floor Intake areas with interview rooms. - All 2nd floor. |
|
09/24/2014 | FIRE - FINAL | Denied | 1. In FACP room found cover on sprinkler head need to correct 2. Need to keep smoke detectors 36" away from intake or exhaust vents correct smokes in the electrical room rooms 1st floor 3. Add visual strobes in conference room on 2nd floor per approved plans 4. Need to test all duct smokes or have paperwork from City Of Tucson mechanical inspector showing testing was completed and passed. 5. Need certificate from the monitoring company showing they are UL/FM approved for monitoring fire equipment. 6. Need FDC sign. 7. Need Riser Room Label. 8. F.D. Key boxes in place and key inside 9. Need gates in place and working 10. Need fire extingushers in place |