Permit: T13CM07726

Parcel: 138170060


Addresses:

324 E ELVIRA RD #J

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/31/2013 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/27/2013 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/27/2013 MECHANICAL - FINAL Denied PROVIDE MIN 3 SCREWS IN ALL JOINTS OF FURNACE & WATER HEATER VENT CONNECTORS. DO NOT USE TAPE. YOU CANNOT REUSE AN OLD GAS FLEX CONNECTOR. PROVIDE A SEDIMENT TRAP IN GAS LINE AT FURNACE. INSULATE SHEET METAL DUCT ABOVE FURNACE. EXTEND VENT 2' ABOVE EVAP COOLER & USE ONLY DOUBLE WALL VENT PIPE. PROVIDE ACCESS TO ROOF.