Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T13CM07712
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/21/2014 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
04/21/2014 | MECHANICAL - ABOVE CEILING | Approved | OK FOR CEILING TILES. NEED TO SEE LETTER FROM ENGINEER TO ALLOW STRAIGHT TAPS | |
04/17/2014 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
04/17/2014 | MECHANICAL - ABOVE CEILING | Partial Approval | SEAL ALL A/C START COLLARS & DUCT CONNECTIONS. ALL FLEX DUCT TO BE SUPPORTED EVERY 5'. PLANS SHOW CONICAL TAPS AT SUPPLY TAKEOFFS, NOT STRAIGHT START COLLARS. NEED TO SEE DUCT SMOKE DETECTORS. PLANS CALL FOR METAL HANGER STRAPS ON FLEX DUCT. |