Permit: T13CM07712

Parcel: 12101103E

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
04/21/2014 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
04/21/2014 MECHANICAL - ABOVE CEILING Approved OK FOR CEILING TILES. NEED TO SEE LETTER FROM ENGINEER TO ALLOW STRAIGHT TAPS
04/17/2014 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
04/17/2014 MECHANICAL - ABOVE CEILING Partial Approval SEAL ALL A/C START COLLARS & DUCT CONNECTIONS. ALL FLEX DUCT TO BE SUPPORTED EVERY 5'. PLANS SHOW CONICAL TAPS AT SUPPLY TAKEOFFS, NOT STRAIGHT START COLLARS. NEED TO SEE DUCT SMOKE DETECTORS. PLANS CALL FOR METAL HANGER STRAPS ON FLEX DUCT.