Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2014 | FIRE - FINAL | Approved | ||
| 06/09/2014 | FIRE - FINAL | Partial Approval | Temp C of O OKAY to use building to get finals the following shall be completed: 1. Remove the roof off of the mezzanine and leave as rack shelving only 2. Install F.D. key boxes |
|
| 06/02/2014 | FIRE - FINAL | Denied | 1. Post address number on building handout given 2. Need fire sprinkler inspection completed pass due 3. Fire extinguishers mounted every 75 foot travel distance and one for every 1500 sq. feet of building 2A-10 BC type and size. 4. Need fire alarm test completed. |