Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - PROGRESS
Permit Number - T13CM07638
Inspection Description - BUILDING - PROGRESS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/26/2014 | BUILDING - PROGRESS | Approved | PER BLDG FINAL | |
| 01/02/2014 | BUILDING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 01/02/2014 | BUILDING - PROGRESS | Not ready for Inspection | 1. REMOVE TAPE FROM FLUE PIPE 2. MINIMUM 3 SCREWS AT FLUE PIPE 3. PROVIDE SECONDARY DRAIN AT COIL 4. NO PVC PIPE WITHIN 6" OF FLUE PIPE 5. CONNECT CONDENSATE PUMP SAFETY SWITCH 6. INSULATE SUPPLY DUCT FROM FURNACE 7. ELEC PLUGS TOO CLOSE TO FLUE PIPE ('B' VENT REQUIRED) 8. PLUMBING & ELEC IN WALL OK TO COVER |