Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2015 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 05/28/2015 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/28/2015 | ELECTRIC - SERVICE UPGRADE | Denied | 1. RISER BRACING TO BE LISTED 2. POWER KILL WAS NEEDED FOR UPGRADE - TEP WILL BE NOTIFIED 3. 2-HOLE STRAP TO BE ANCHORED WITH #10 SCREWS, NOT SHEETROCK SCREWS 4. CHASE NIPPLE USED ON SERVICE NOT INSTALLED TO CODE 245 5. TWO GROUND RODS MISSING FOR UPGRADE 6. SERVICE PANEL NOT TO BE USED FOR J-BOX. GROUNDS AND NEUTRALS TO BE SEPARATED |