Permit: T13CM07542

Parcel: 126190940


Addresses:

4340 E EASTLAND ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/29/2015 ELECTRIC - SERVICE UPGRADE Approved
05/28/2015 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/28/2015 ELECTRIC - SERVICE UPGRADE Denied 1. RISER BRACING TO BE LISTED
2. POWER KILL WAS NEEDED FOR UPGRADE - TEP WILL BE NOTIFIED
3. 2-HOLE STRAP TO BE ANCHORED WITH #10 SCREWS, NOT SHEETROCK SCREWS
4. CHASE NIPPLE USED ON SERVICE NOT INSTALLED TO CODE 245
5. TWO GROUND RODS MISSING FOR UPGRADE
6. SERVICE PANEL NOT TO BE USED FOR J-BOX. GROUNDS AND NEUTRALS TO BE SEPARATED