Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2014 | FIRE - FINAL | Approved | ||
| 08/11/2014 | FIRE - FINAL | Denied | 1. FDC is blocked by a wall therefore will need to post a FDC sign on wall showing location, sign needs 6" red letters on a white reflective background. 2. Need locks outs on fire bell and fire alarm breakers so as one can turn the power off. 3. Smoke detector in bedroom #10 did not sound when tested with other smokes, when testing the smoke detector in that room only it sounded but did not sound throughout the other smokes; need to interconnect all smokes to each other. 4. Advance alarm needs a permit and call in for a final for the fire alarm system. |