Permit: T13CM07348

Parcel: 136241440


Addresses:

6725 E DAVID DR

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
02/10/2014 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
01/30/2014 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/30/2014 ELECTRIC - RECONNECT Denied 1. SERVICE WIRES IN RISER INSULATION DETERIORATING, CRACKED, & COMING OFF. ALSO, TOO LOW
2. GET PERMIT FOR UPGRADE
01/21/2014 ELECTRIC - RECONNECT Denied 1. FRONT DOOR OUTISDE LIGHT AND CARPORT LIGHT WIRES TO BE CAPPED OFF
2. SERVICE WIRES TO BE REPLACED AN RAISED TOO LOW 230.24B
3. CODE DOESN'T WORK
4. SMOKE DETECTORS IN BEDROOMS AND HALLWAYS MISSING
5. OUTLET AND SWITCH COVERS PLATES MISSING
01/17/2014 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/06/2013 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/06/2013 ELECTRIC - RECONNECT Denied 1. FRONT DOOR OUTSIDE LIGHT & CARPORT LIGHT WIRES TO BE CAPPED OFF
2. SERVICE WIRES TO BE REPLACED & RAISED - TOO LOW - 230.24.B
3. CODE DOESN'T WORK