Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T13CM07286
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/20/2014 | FIRE - FINAL | Approved | ||
03/18/2014 | FIRE - FINAL | Denied | 1. Replace all painted upright sprinkler heads throughout the building 2. Rear storage room one head blocked by a light and sewer piping north east corner need to cooorect. 3. Correct upright sprinkler coverage in dressing room area per approved sprinkler plans. 4. Correct blocked head upright above bathroom. 5. Mount 2 fire extingushers for business 2A-10BC type. |