Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T13CM07286
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/20/2014 | FIRE SPKLR - FINAL | Approved | ||
03/18/2014 | FIRE SPKLR - FINAL | Denied | 1. Replace all painted upright sprinkler heads throughout the building 2. Rear storage room one head is blocked by a light and sewer piping north east corner need to correct. 3. Correct upright sprinkler coverage in dressing room area per approved sprinkler plans. 4. Correct blocked head upright above bathroom. |