| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/15/2014 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/02/2014 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 01/02/2014 | ELECTRIC - SERVICE UPGRADE | Partial Approval | 1. ISOLATE GROUNDS/NEUTRALS IN SUBPANEL 2. PROVIDE BOND BUSHING ON 2" NIPPLE BETWEEN METER BASE & PANEL. 250-NEC 3. LABEL CIRCUIT BREAKERS IN PANELS **RESCHEDULE INSPECTIONS** |