Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2014 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/04/2014 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/04/2014 | ELECTRIC - INTERMEDIATE | Denied | 1. ROMEX TO BE SUPPORTED TO CODE 12" & 4'. RECEPTACLE/SWITCH BOXES TO HAVE APPROVED CABLE CONNECTORS. GROUNDS CUT OFF OF CABLING? 2. AIR HANDLER REQUIRES DISC SWITCH AT UNIT 3. SE CABLE TO HAVE APPROVED CONNECTORS AT ALL TERMINATIONS. ALSO, ROMEX INTO PANELS, J-BOXES, ETC... HOW DID YOU MAKE SPLICE FROM SINGLE CONDUCTORS TO SE CABLE? 4. PROVIDE LADDER FOR ROOF INSPECTION |