Permit: T13CM07176

Parcel: 132171390

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
01/24/2014 FIRE - FINAL Approved
12/31/2013 FIRE - FINAL Denied Ch. 7 IFC 2012 ED. Field notice given for improperly in stalling R-30 insulation in the ceiling having the paper backing exposed in the open, as printed on backing states "not to leave the backing exposed". Will need to properly install the insulation per manufacture and code requirements and keep a 1 inch clear plane above all sprinkler heads throughout the building.
Field notice given for pass due annual sprinkler inspections and 5 year check valve inspections, C of O will not be approved until completed.