Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
| Date |
Description |
Inspector |
Results |
Comments |
| 02/11/2016 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Approved |
already approved. see sprink permit. |
| 11/05/2014 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Cancelled |
IVRS - RI canceled |
| 10/09/2014 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Cancelled |
IVRS - RI canceled |
| 10/07/2014 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Partial Approval |
200 PSI for 2 hours for 45 feet of 6 inch underground main for sprinkler supply, still need to flush line. Still need to test the FDC line at 200 PSI for 2 hours and flush. |
| 09/30/2014 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Cancelled |
SAME AS 09.29.2014 |