Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2013 | ELECTRIC - FINAL | Approved | ||
| 12/11/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/11/2013 | ELECTRIC - FINAL | Denied | ID ALL BREAKERS, MAX 15 AMP BREAKER FOR #14 WIRE, PROVIDE WEATHER-PROOF FITTING AT TOP OF NEW PANEL, MOVE SIDE INLET E.M.T. ITS INTERFERING WITH DEAD FRONT | |
| 12/10/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 12/10/2013 | ELECTRIC - FINAL | Partial Approval | LINE SIDE ONLY RECALL FOR LOAD SIDE |