Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T13CM06968
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/22/2017 | BUILDING - FINAL | Approved | APPROVED | |
11/21/2017 | BUILDING - FINAL | Not ready for Inspection | ||
11/20/2017 | BUILDING - FINAL | Denied | MISSING UN-SCREWABLE SAFETY CAPS ON COMPRESSOR POMPRESSOR MAX AMP FUSE IS 20 AMP MISSING GFCI ON COUNTER MISSING ANIT-SIPHONS ON HOSE BIBS MISSING CERTS. |
|
11/07/2017 | BUILDING - FINAL | Partial Approval | MOVED THE SERVICE METER PER TEP. |