Permit: T13CM06926

Parcel: 133320780


Addresses:

511 N GOLLOB RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T13CM06926

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/22/2013 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/15/2013 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/15/2013 ELECTRIC - FINAL Denied CLOSE 2 OPENED KNOCKOUTS IN BOTTOM OF PANEL. PROVIDE A SMOKE DETECTOR IN EACH BEDROOM. DETECTOR IN HALL DOES NOT WORK. PROPERLY TERMINATE CONDUCTORS AT POOL PUMP. PROVIDE A WEATHER-PROOF BOX & GFI RECEPTACLE AT PATIO RECEPTACLE OR REMOVE. PROVIDE GFI AT WATER SOFTENER RECEPTACLE OR REMOVE.