Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/13/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/13/2013 | ELECTRIC - FINAL | Denied | NEW SERVICE INSTALLED WITHOUT PERMITS. PROVIDE 2-8' GROUND RODS MIN 6' APART. PROVIDE 2 LISTED CLAMPS ON MAST ABOVE PANEL. PROVIDE A LISTED BRACE KIT ON ROOF. ADD ELEC UPGRADE TO PERMIT. CORRECTIONS HAVE BEEN MADE FROM PREVIOUS RECONNECT INSPECTION. |