Permit: T13CM06794

Parcel: 13216639A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T13CM06794

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/14/2014 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/27/2013 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/27/2013 ELECTRIC - FINAL Denied - CONDUCTORS #4 & LARGER REQUIRES BUSHINGS AT TERMINATION 300.4 NEC
- OVER 250 VOLTS REQUIRES BOND BUSHINGS AT CONCENTRICS 250 NEC
- DISC SWITCHES AT MOTORS REQUIRES 36" IN FRONT BY 30" HORIZONTAL WORKING CLEARANCE PER 110.26 NEC
- SUPPORT 1 1/2" CONDUITS IN EQUIP ROOM