Inspection History: FIRE - FINAL
Permit Number - T13CM06793
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/21/2014 | FIRE - FINAL | Approved | Appeal approved concerning hardware. All other fire concerns addressed. | |
05/22/2014 | FIRE - FINAL | Denied | Need panic hardware on front main entrance Per Approved plans PG A701 under general notes #5 and IBC & IFC 1008.1.9.3 they do not meet any subsections, because occupant load is 417. | |
04/23/2014 | FIRE - FINAL | Partial Approval | Temp Cof O Approved to get finials the following will need to be Completed: 1. For hood system final plans do reflect what is on site missing one deep fryer and no oven in place duct work is 10" x 22" and other one is 10 ½" X 22", one grill is smaller and nozzle was changed out also will need to have the system monitored. Need resubmittals on plans to show what appliances are installed under hood and all nozzles match. 2. For alarm final need separate plan and permit for alarm system, hood system, tamper, water flow, and duct detectors. 3. For sprinkler final need sectional valve tamper switch and water flow monitored. (Located in the stairwell) 4. Install fire department key system - need access key into bussines. 5. Limit roll down screen to 78" or more in height for patio gate on westside. |