Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/23/2014 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection :* |
| 01/23/2014 |
ELECTRIC - ABOVE CEILING |
|
Approved |
OK FOR CEILING TILES EXCEPT AREAS OF HOT WATER PIPING & CONDENSATE DRAIN LINE. |
| 01/21/2014 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 01/21/2014 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
SECURE LIGHTS TO GRID. SUPPORT ELEC CONDUITS. ELEC BOXES ABOVE CEILING NOT FINISHED. ISOLATE COPPER FROM STEEL FRAMING. GROUNDING ELECTRODE HAS BEEN VANDALIZED. |