Permit: T13CM06688

Parcel: 110071830

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T13CM06688

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/12/2013 PLUMBING - FINAL Approved IVRS - Inspection :*
11/12/2013 PLUMBING - FINAL Approved 10 PSI TEST IS OK. LEFT GAS CARD. CORRECTIONS HAVE BEEN MADE.
11/04/2013 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/04/2013 PLUMBING - FINAL Denied PROVIDE DOUBLE WALL VENTING AT WATER HEATER PENETRATION THROUGH ROOF W/ MIN 1" CLEARANCE. PROVIDE A 90 DEGREE ELBOW AT T & P DRAIN TERMINATION. PROVIDE MIN 3 SCREWS IN EACH JOINT OF VENT CONNECTOR. PROVIDE ACCESS TO ROOF. PROVIDE A MIN 10LB TEST ON A 15 LB GAUGE. PROVIDE ELEC BOND TO GAS PIPING.