Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T13CM06688
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/12/2013 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
11/12/2013 | PLUMBING - FINAL | Approved | 10 PSI TEST IS OK. LEFT GAS CARD. CORRECTIONS HAVE BEEN MADE. | |
11/04/2013 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
11/04/2013 | PLUMBING - FINAL | Denied | PROVIDE DOUBLE WALL VENTING AT WATER HEATER PENETRATION THROUGH ROOF W/ MIN 1" CLEARANCE. PROVIDE A 90 DEGREE ELBOW AT T & P DRAIN TERMINATION. PROVIDE MIN 3 SCREWS IN EACH JOINT OF VENT CONNECTOR. PROVIDE ACCESS TO ROOF. PROVIDE A MIN 10LB TEST ON A 15 LB GAUGE. PROVIDE ELEC BOND TO GAS PIPING. |