Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2014 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/30/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/30/2014 | MECHANICAL - FINAL | Denied | MARK UNIT DATA PLATE W/ PROPER HEAT STRIP & FUSE ACCORDINGLY. 20 AMP FUSES WILL NOT WORK FOR ANY OF THE HEATERS LISTED ON DATA PLATE. 35 AMP WOULD BE THE ONLY FUSE YOU COULD USE FOR 5KW HEATER. SECURE THE ELEC DISCONNECT. |