Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T13CM06642

Parcel: 11007414D

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T13CM06642

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/31/2013 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/27/2013 MECHANICAL - FINAL Not ready for Inspection FOR MECH FINAL, FINISH CONDENSATE ON ROOF. UNITS ARE OVERFUSED. I.D. UNITS ON ROOF. PAINT EXPOSED PLASTIC ON ROOF W/ LATEX PAINT. PROVIDE AIR BALANCE REPORT.