Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T13CM06642
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/13/2013 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/12/2013 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
11/12/2013 | PLUMBING - INTERMEDIATE | Not ready for Inspection | CONDENSATE FROM ANOTHER SUITE CANNOT TERMINATE INTO THIS SUITE. PLEASE POST A SUITE NUMBER AT ENTRY. BE SURE TO PROVIDE THE LAV CARRIER AS SPECIFIED. FINISH PLUMBING IN WALLS. PROVIDE CONDENSATE DRAIN AS PER PLAN. |