Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/25/2013 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 11/08/2013 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
| 11/08/2013 | PLUMBING - ROUGH, SOIL | Partial Approval | NO PIPING SHALL BE TESTED W/ LESS THAN 10' OF HEAD. FLOOR TEST FITTING TO REMAIN UNTIL TEST THRU ROOF IS COMPLETE. | |
| 11/07/2013 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/07/2013 | PLUMBING - ROUGH, SOIL | Denied | PLUMBING FLOOR PLAN #1 SHOWS A CLEANOUT FOR YOUR WC. THIS CO SHALL BE THE SAME SIZE AS THE WASTE LINE, 3". NO FITTING SHALL BE TESTED W/ LESS THAN 10' HEAD. INSTALL YOUR CLEANOUT FITTINGS AND TEST THROUGH THEM SO THAT YOU MAY COVER YOUR ONLY TEST FITTING LOCATED BELOW SLAB. |