Permit: T13CM06642

Parcel: 11007414D

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
11/25/2013 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
11/08/2013 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
11/08/2013 PLUMBING - ROUGH, SOIL Partial Approval NO PIPING SHALL BE TESTED W/ LESS THAN 10' OF HEAD. FLOOR TEST FITTING TO REMAIN UNTIL TEST THRU ROOF IS COMPLETE.
11/07/2013 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/07/2013 PLUMBING - ROUGH, SOIL Denied PLUMBING FLOOR PLAN #1 SHOWS A CLEANOUT FOR YOUR WC. THIS CO SHALL BE THE SAME SIZE AS THE WASTE LINE, 3". NO FITTING SHALL BE TESTED W/ LESS THAN 10' HEAD. INSTALL YOUR CLEANOUT FITTINGS AND TEST THROUGH THEM SO THAT YOU MAY COVER YOUR ONLY TEST FITTING LOCATED BELOW SLAB.