Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2014 | FIRE - FINAL | Approved | ||
| 02/12/2014 | FIRE - FINAL | Denied | Tested curtains by each exit way and stage by cutting a piece of the curtain and then using a match until the material starts burning and then remove the match all samples kept burning did not go out. I then cut a curtain that was lying on the floor and has labels stating that it's treated put the match to it until it started burning and remove the match from material and it stopped burning immediately. Told owner that they need to buy new curtains or re-treat again and test for burning. | |
| 02/05/2014 | FIRE - FINAL | Denied | 1. All curtains and wall decorations shall be fire-retardant 2. Repair emergency lighting by restroom 3. Install emergency lighting over exit door by speedway side 4. Adjust emergency lighting to shine down on exit way not on ceiling 5. Keep clear exit egress path to rear door on speedway side at all times move couch out of pathway and keep storage down to what is needed for the shows only no storage allowed 6. Post Occ. Load sign by main doors parking lot side 104 per approved plans |