Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/14/2014 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 01/14/2014 |
ELECTRIC - FINAL |
|
Approved |
PROVIDE A SCREEN IN EXHAUST FAN T-TOP ON ROOF. PROVIDE FILTERS IN FRESH AIR INTAKES. CODE REQUIRES THE USE OF PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE. SLOPE CONDENSATE DRAINS MIN 1/8" PER FT. ELEC CONDUITS TO A/C UNITS ON ROOF ARE COMING APART. PROVIDE AIR BALANCE REPORT. |