Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/18/2013 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 10/30/2013 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/30/2013 | PLUMBING - GAS PRESSURE TEST | Denied | NOT A RECONNECT, PIPING IS NEW. PIPING MAY NOT BE INSTALLED BELOW SLAB W/OUT SLEEVING, VENTED TO EXTERIOR. WH NOT YET INSTALLED. FURNACE NOT CONNECTED. GAS SOV & FLEX ALSO SEDIMENT TRAP REQ. CORRECT CONDENSATE INSTALL A CARBON MONOXIDE DETECTOR. **NOTE: NEW ELECTRICAL & PLUMBING REQ REPORTS** |